Three Phase Power Meter Ht-305
-
Price:
Negotiable
- minimum:
- Total supply:
-
Delivery term:
The date of payment from buyers deliver within days
-
seat:
Jiangsu
-
Validity to:
Long-term effective
-
Last update:
2017-09-23 02:55
-
Browse the number:
317
+
Jinhu Hanton Instrument and Meter Co., Ltd.
- Contactaixin:
Mr. Raymond(Mr.)
- Email: telephone: phone:
-
Arrea:
Jiangsu
Address:19f, Peace Mansion, No. 22 East Beijing Rd, Nanjing, Jiangsu, China 210008
- Website:
+
Three phase four wire/ three wire remote rate controlled smart meter is an internationally advanced electric energy measuring meter designed, manufactured according to residence actual electric consumption, adopting digital sampling and processing technology and SMT technology and using advanced electric energy measuring special chip. All components inside the meter are selected by longest life period, high reliability which becomes the features of the meter.
This product meets the standards of I IEC 62053-22 (Class 0.2S, Class 0.5S) / IEC 62053-21(Class 1)
Communication protocol meets the requirements of IEC62056-21, IEC62056-61, and DLMS/COSEM.
This product has communication interfaces of modulated infrared, RS485, PLC and wireless M-BUS, easy to have field meter reading as well as remote meter reading. All communication data of the interfaces are encrypted.
This meter can support both IEC 61334 and PRIME PLC communication, IEC61334 adopts S-FSK technology, and the speed is 2.4Kbps, and PRIME speed can be from 21.4 to 128.6kbps.
Item |
Technical data |
Frequency |
45Hz-65Hz |
Class |
0.2s,0.5s,0.5,1.0,2.0 |
Rated voltage(V) |
3x57.7/100V,3x230/400V |
Rated current(A) |
3x1.5(6)A,3x15(100)A |
Constant(imp/kWh) |
20000 64000 800 |
Specified working voltage range |
0.9Un-1.1Un |
Expanded working voltage range |
0.8Un-1.15Un |
Limited working voltage range |
0.0Un-1.15Un |
Starting current( DC), Class1.0 |
0.004Ib. |
Starting current( DC), Class0.5S |
0.002Ib. |
Starting current(CT/PT), Class1.0 |
0.002Ib. |
Starting current(CT/PT), Class0.5S |
0.001Ib. |
Starting current(CT/PT), Class0.2S |
0.001Ib. |
Specified working temperature range |
-30ºC~+70ºC |
limited working temperature range |
-40ºC~+80ºC |
Limiting temperature of storage and transportation | -40ºC~+80ºC |
Annual average relative humidity | <75% |
Humidity of natural distribution of 30 days within one year | 95^ |
Humidity of occasional appear in other days | 85% |
LCD display of energy data | 0-999999.99kWh, 0-999999.99kvarh. |